Overview

The Single Relay Output e-Controller® unit is a device featuring a relay type output that includes special high rupture capacity contacts that can take up to 8 Amp loads. This device takes advantage of the mains wiring as the means for data transmission, over which it receives information from one or more transmitters in order to operate its output. Since data transmission takes place over the installation mains wiring, no additional wiring is required to connect the units, thus avoiding the associated costs. Furthermore, this allows fitting the device in already existing buildings.

Ordering number: 
EC.510102-000
Supply input: 95-250Vac
Technology: LonWorks
Field bus: PowerLine
Number of outputs: 
1
Outputs names: 
8 A relay output
Operation: 

Based on the EN 14908 LonWorks® communication standard, the e-Controller® product series takes advantage of the mains wiring as a means to transmit data, thus allowing the installer to conveniently locate equipment throughout the installation without the need to plan ahead for wiring between the various facility elements, such as lights, socket controls, solenoid valves or other loads.

LonWorks® PowerLine technology provides robust and reliable communication in compliance with CENELEC, Band C standards (residential and commercial applications).

Installation

System installation does not require additional wiring, dramatically reducing installation time and cost and providing an optimal solution for building refurbishment or rehabilitation. No computer or special software is necessary to configure the unit, rendering this solution even more versatile and easy to install.

Based on the ISO/IEC (LonWorks®) communication standard, this device may be integrated into any LonMark® system in the market.

Integration

Device commissioning may be performed in either of two ways:

1) Self installation: The device includes an advanced self installation algorithm that provides for device commissioning with no computer or special software required. Through a pushbutton located on its front, the unit may be installed and allocated to a keypad, a presence or luminosity sensor or to any other device present in the network that may remotely control the unit.

2) Installation with LNS compatible tools: The device includes an XIF file documented network interface that allows integration into any LonWorks facility. The device is LonMark compatible and includes the standard functional profiles as prescribed by the standards; they allow seamless integration of the device into any LonWorks network where equipment by other manufacturers may be present.

Downloads

| | Product Features Document
| | 1 | Device wiring installation | Documento para instalación del producto
| | 0 | Product dimensions | Documento para instalación del producto
| | 1 | LonWorks integration file | Documento XIF para integración con herramienta LNS compatible